    The testo 320 combustion analyzer, offering comprehensive combustion system analysis, is designed for the job site and for the contractor who expects more. Use the Testo combustion analyzer for basic testing and tuning of all types of boilers, heaters or furnaces and also to set up and commission more complex multi-stage or modulating heating systems, for accurate combustion efficiency analysis.

  • Download Feedback
  • Prev:testo 330-1G LL Kit 1 - Flue gas analysis kit

    Next:testo 310 - Residential combustion analyzer kit

  • Description
  • Details
  • Optional Accessories
  • Product Description

    The testo 320 combustion analyzer, offering comprehensive combustion system analysis, is designed for the job site and for the contractor who expects more. Use the Testo combustion analyzer for basic testing and tuning of all types of boilers, heaters or furnaces and also to set up and commission more complex multi-stage or modulating heating systems, for accurate combustion efficiency analysis.


    Innovative features like the flue gas matrix will graphically display the combustion characteristics, which is an easy way to show if the heating system is running efficiently. Additionally the testo 320 makes the job easier by displaying from two to eight user-defined parameters simultaneously. The testo 320 eliminates the guess work and provides accurate combustion system analysis.


    Comprehensive combustion efficiency analysis:

    O2, CO (with built-in NOx filter), CO2

    Combustion calculations

    Draft

    Pressure

    Flue gas matrix

    User-changeable, pre-calibrated sensors that are easy to replace

     

    Delivery Scope

    320 combustion analyzer with rechargeable battery, 12 inch probe with cone and hose, AC power supply (with USB recharging), spare particulate filters (10), and rugged case


  • Differential Pressure

    Measuring range±40 InH?O / ±10000 Pa
    Accuracy

    ±0.0 InH?O (0 to 0.04 InH?O) plus ±1 Digit / ±0.3 Pa (0 to 9.99 Pa) plus ±1 Digit

    ±3 % of mv (0 to 40 InH?O) plus ±1 Digit / ±3 % of mv (10 to 10000 Pa) plus ±1 Digit

    Flue gas O?

    Measuring range0 to 21 Vol.%
    Accuracy±0.2 Vol.%
    Resolution0.1 Vol.%
    Reaction time t??< 20 sec

    Flue gas CO

    Measuring range0 to 8000 ppm
    Accuracy

    ±10 ppm or ±10 % of mv (0 to 200 ppm)

    ±20 ppm or ±5 % of mv (201 to 2000 ppm)

    ±10 % of mv (2001 to 8000 ppm)

    Resolution1 ppm
    Reaction time t??< 40 sec


    Flue gas COlow

    Measuring range0 to 500 ppm
    Accuracy

    ±2 ppm (0 to 39.9 ppm)

    ±5 % of mv (40 to 500 ppm)

    Resolution0.1 ppm
    Reaction time t??< 40 sec

    Flue Gas Draft

    Measuring range-4.00 to +16 InH?O / -9.99 to +40 hPa
    Accuracy±0.01 InH?O or ±5 % of mv (-0.20 to +0.24 InH?O) / ±0.02 hPa or ±5 % of mv (-0.50 to +0.60 hPa)

    ±0.01 InH?O (+0.24 to +1.20 InH?O) / ±0.03 hPa (+0.61 to +3.00 hPa)

    ±1.5 % of mv (+1.20 to +16.00 InH?O) / ±1.5 % of mv (+3.01 to +40.00 hPa)

    Resolution0.00 InH?O with fine draught option 0.000 InH?O / 0.01 hPa with fine draught option 0.001 hPa

    Temperature

    Measuring range-40° to 2192 °F / -40 to +1200 °C
    Accuracy

    ±0.9 °F (32° to 212.0 °F) / ±0.5 °C (0 to +100.0 °C)

    ±0.5 % of mv (Remaining Range)

    Resolution

    0.1 °F (-40° to 1831.8 °F) / 0.1 °C (-40 to +999.9 °C)

    1.0 °F (> +1832 °F) / 1 °C (> +1000 °C)

    Efficiency (calculated)

    Measuring range0 to 120 %
    Resolution0.1 %

    Flue Gas loss (calculated)

    Measuring range0 to 99.9 %
    Resolution0.1 %

    Flue Gas CO? calculation (calculated from O?)

    Measuring range0 to CO? max (Display range)
    Accuracy±0.2 Vol.%
    Resolution0.1 Vol.%
    Reaction time t??< 40 sec

    Velocity / Volume flow

    Measuring range29.50 to 591 fpm / 0.15 to 3 m/s
    Resolution0.1 fpm / 0.1 m/s

    Pressure measurement

    Measuring range0 to +120 InH?O / 0 to +300 hPa
    Accuracy

    ±0.2 InH?O (0.0 to 20.0 InH?O) / ±0.5 hPa (0.0 to 50.0 hPa)

    ±1 % of mv (20.0 to 40.0 InH?O) / ±1 % of mv (50.1 to 100.0 hPa)

    ±1.5 % of mv (Remaining Range)

    Resolution0.1 InH?O with fine pressure option 0.01 InH?O / 0.1 hPa with fine pressure option 0.01 hPa

    Flue gas CO (without H?-compensation)

    Measuring range0 to 4000 ppm
    Accuracy

    ±20 ppm (0 to 400 ppm)

    ±5 % of mv (401 to 2000 ppm)

    ±10 % of mv (2001 to 4000 ppm)

    Resolution1 ppm
    Reaction time t??< 60 sec

    Ambient CO

    Measuring range0 to 500 ppm
    Accuracy

    ±5 ppm (0 to 100 ppm)

    ±5 % of mv (> 100 ppm)

    Resolution1 ppm

    with CO probe

    Ambient CO?

    Measuring range

    0 to 1 Vol.%

    0 to 10000 ppm

    Accuracy

    ±50 ppm or ±2 % of mv (0 to 5000 ppm)

    ±100 ppm or ±3 % of mv (5001 to 10000 ppm)

    with ambient CO? probe

    Gas leak measurement for combustible gases (via gas leak detection probe)

    Measuring range0 to 10000 ppm CH? / C?H?; Display range
    AccuracySignal optical display (LED) audible signal via buzzer
    Reaction time t??< 2 sec

    with gas leak detection probe

    Temperature (via the fine pressure probe)

    Measuring range-40° to 2192 °F / -40 to +1200 °C max. (dependent on probe)
    Accuracy

    ±0.9 °F (-40° to 212 °F) / ±0.5 °C (-40 to 100 °C)

    ±0.5 % of mv (Remaining Range) plus probe accuracy

    Resolution0.1 °F / 0.1 °C

    General technical data

    Dimensions9 x 3 x 3 in. / 240 x 85 x 65 mm
    Operating temperature23° to 113 °F / -5 to +45 °C
    WarrantyInstrument: 24 months; Probe: 24 months; Gas sensors: 24 months; rechargeable battery: 12 months
    Display size240 x 320 pixels
    Display functionColour graphic display
    Power supplyBattery: 3.7 V / 2,400 mAh; Mains unit: 6 V / 1.2 A
    Maximum500 Measurement values
    Storage temperature-4° to 122 °F / -20 to +50 °C
    Weight20 oz. / 573 g